Smart Laboratories at the University of California, Irvine
Matt Gudorf, LEED® AP, University of California, Irvine
Marc Gomez, LEED AP, Ballinger
The "Smart Labs" concept is an integrated approach to energy consumption reduction and sustainability in energy intensive research space on university campuses. The goal in applying the Smart Labs features is to reduce overall annual energy consumption by 50 percent.
Exhaust Stack Discharge Velocity Reduction (ESDVR) looks to reduce laboratory exhaust stack velocity and eliminate bypass air by re-evaluating the original building wind tunnel study and performing additional wind tunnel testing to avoid reentrainment and contamination of occupied spaces. Exhaust stacks may be modified to allow for increased plume dispersion and decreased energy consumption.
Centralized demand controlled ventilation looks at real-time, indoor air quality in the occupied spaces and varies the ventilation rates accordingly. This allows for significant air change rate setbacks during times of low process activity.
High performance fume hoods allow for improved containment with the potential to reduce face velocity from 100 feet-per-minute to approximately 70 feet-per minute based on a study conducted at University of California, Irvine in conjunction with the California Occupational Safety and Health Administration.
Smart lighting in laboratory space with daylighting opportunities use controls to step dim light levels when adequate natural light is available. Perforated blinds are used in these spaces to diffuse direct sunlight but allow for partial daylight penetration. Occupancy sensing is used in a bay-by-bay configuration for maximum segmentation.
Where possible, ENERGY STAR® qualified equipment should be used. This includes freezers, refrigerators, ice machines, and copiers.
Features of our newest Smart Labs building, Gross Hall, will be shared including, centralized demand controlled ventilation, step dimming capability to respond to daylighting opportunities, and operable windows in office spaces encourage the use of natural ventilation to improve indoor air quality. Air handlers are designed with a low face velocity across the coils and are equipped with deep pleat, high media surface area, MERV 14 filters to reduce system pressure drop and fan motors run on variable frequency drives. Exhaust fans are high plume vector type fans with induced flow and right sized to take advantage of fan law savings through running multiple fans at a slower speed on variable frequency drives. The HVAC design also includes cascade cooling through transfer grills to secondary spaces to eliminate the need for fan-coil units.
Next, we plan to measure Gross Hall's energy savings performance against Hewitt Hall, a new and efficient laboratory building, by metering the buildings and comparing key metrics.
Biographies:
Matt Gudorf is the energy project manager at the University of California at Irvine and a LEED Accredited Professional with 10 years of infrastructure project management experience. A graduate of The Ohio State University in electrical engineering with an emphasis on high voltage systems, Mr. Gudorf has worked for Dayton Power and Light in transmission and distribution, American Electric Power as a member of the ultra high voltage substation design team, and Southern California Pipeline managing multiple wet utility projects throughout Southern California. Mr. Gudorf has focused his efforts at the University of California, Irvine on energy efficiency upgrades, utility and infrastructure retrofits, and project development.
Marc Gomez is the interim assistant vice chancellor of facilities management and environmental health and safety at the University of California, Irvine. He has more than 27 years of experience working in private industry, health care and the academic environment. Mr. Gomez holds certifications in industrial hygiene, safety, and risk management. He has a Master of Public Health from the University of Michigan.